Alnor EBT Balometer Capture Hood EBT731
Are you buying in volume? Are you an OEM? Are you a reseller? Be sure to contact FLW directly for your special pricing.
Description
TSI Alnor EBT731 has been granted California Energy Commission Title 24 approval.
The TSI Alnor EBT731 Balometer® Capture Hood is an electronic air balancing multipurpose instrument mainly used to take direct air volume readings at diffusers and grilles. The EBT731 features a detachable micromanometer which can be used with optional probes for increased flexibility in multiple measurement applications.The easy-to-use EBT731 is a lightweight and ergonomically designed capture hood kit which conveniently provides multiple measurement tools in one package. The EBT731 Balometer Capture Hood provides you the capability to produce energy efficient environments while staying within guidelines and regulations for ventilation systems.
Included Items
- 2 ft x 2 ft. (610 mm x 610 mm) air capture hood/frame/base
- Manometer with carrying case
- (4) AA size rechargeable NiMH batteries
- Multi-country AC adapter
- 18in. (46 cm) Pitot probe
- (2) Static Pressure probes
- 16 ft (4.8 m) Neoprene tubing
- Wheeled luggage-style carrying case
- NIST traceable calibration certification
- Downloading software
- USB interface cable
- Manual
Product Specifications
Velocity Range
Pitot probes: | 25 to 15,500 ft./min (0.125 to 78 m/s) |
Air flow probe: | 25 to 5,000 ft./min (0.125 to 25 m/s) |
Velocity matrix: | 25 to 2,500 ft./min (0.125 to 12.5 m/s) |
Accuracy: | ±3% of reading ±7ft./min (±0.04 m/s) at velocities >50 ft./min (>0.25 m/s) |
Units: | ft./min, m/s |
Resolution: | 1 ft./min (0.01 m/s) |
Differential pressure: | ±15 in. H20 (±3735 Pa); 150 in. H20 (37.5 kPa), maximum safe operating pressure |
Absolute pressure: | 15 to 40 in Hg (356 to 1016 mm Hg) |
Accuracy: | ±2% of reading ±0.0001 in. H20 (±0.025 Pa) static and differential; ±2% of reading absolute |
Units: | in. H20, in. Hg, Pa, hPa, kPa, mm Hg, cm Hg, mm H20, cm H20 |
Resolution: | 0.00001 in. H20 (0.001 Pa) static and differential; 0.01 in. Hg (1 mm Hg) absolute |
Range: | 25 to 2,500 ft.³/min (42 to 4250 m³/h) capture hood, supply and return |
Accuracy: | ±3% of reading ±7 ft.³/min (± m³/h) at flows >50ft.³/m (>80 m³/h) |
Units: | 1 ft.³/min, m³/h, m³/min, l/s |
Resolution: | 1 ft.³/min (1 m³/h) |
Range: | 5 to 95% RH (temperature/RH probe) |
Accuracy: | ±3% RH |
Resolution: | 0.1% RH |
Sensor in base: | 40 to 140°F (4.4 to 60°C) |
Temperature/RH probe: | 14 to 140°F (-10 to 60°C) |
Accuracy: | ±0.5°F (±0.3°) |
Units: | °F, °C |
Resolution: | 0.1°F (0.1°C) |