ATC Universal Two Mode Timer, 657-8-4000
$157.40
Are you buying in volume? Are you an OEM? Are you a reseller? Be sure to contact FLW directly for your special pricing.
Description
The 657-8-4000 timer has two (2) user selectable modes of operation; ON Delay and Interval. In either operation mode the user can select from 2 output contact configurations; 2 timed contacts or 1 timed contact and 1 instantaneous contact. Selection of the operating mode and contact output configuration choice provides the user with timing control versatility.
Features:
Features:
- 2 SPDT 10A @ 120 VAC Relays
- Universal Input Power 85-240 VAC/DC
- LED Indicators - Show Operating Status and Relay Contact Status
- Six (6) Time Bases From 0.1 Second to 127 Hours
- Convenient Top Mounted Time Setting Switches
- Extremely Cost Effective
Product Specifications
General Specifications
Timing Ranges: | 0.1â12.7 SEC 0.1â12.7 MIN 0.1â12.7 HR 1.0â127 SEC 1.0â127 MIN 1.0â127 HR |
---|---|
Time Setting Method: | DIP Switches Located On Top |
Reset Times: | 50 mSEC Max |
Operating Power: | Universal, 85-240 VAC or VDC |
Repeat Accuracy: | ± 0.002% of Timed Setting |
Relay Outputs: | 2 Each, SPDT Form C 10A @ 120 VAC, 5A @ 240 VAC / 30 VDC |
Power Consumption: | 30mA Max. |
Operating Temperature: | 32° to 122°F (0° to 50°C) |